APC : 001,051,1253 DATE : 2012-05-20 22:29:36 +0300 HOSTNAME : kosmos.kuntsi.com VERSION : 3.14.10 (13 September 2011) debian UPSNAME : SERVER CABLE : Custom Cable Smart DRIVER : APC Smart UPS (any) UPSMODE : Stand Alone STARTTIME: 2012-05-12 18:57:12 +0300 MODEL : SMART-UPS 1000 STATUS : ONLINE LINEV : 234.0 Volts LOADPCT : 10.9 Percent Load Capacity BCHARGE : 100.0 Percent TIMELEFT : 8.0 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds MAXLINEV : 236.6 Volts MINLINEV : 232.7 Volts OUTPUTV : 234.0 Volts SENSE : High DWAKE : 000 Seconds DSHUTD : 020 Seconds DLOWBATT : 02 Minutes LOTRANS : 196.0 Volts HITRANS : 253.0 Volts RETPCT : 000.0 Percent ITEMP : 39.1 C Internal ALARMDEL : 5 seconds BATTV : 27.6 Volts LINEFREQ : 50.0 Hz LASTXFER : Automatic or explicit self test NUMXFERS : 0 TONBATT : 0 seconds CUMONBATT: 0 seconds XOFFBATT : N/A SELFTEST : NO STESTI : 336 STATFLAG : 0x07000008 Status Flag DIPSW : 0x00 Dip Switch REG1 : 0x00 Register 1 REG2 : 0x00 Register 2 REG3 : 0x00 Register 3 MANDATE : 11/16/99 SERIALNO : QS9947311604 BATTDATE : 20/04/11 NOMOUTV : 230 Volts NOMBATTV : 24.0 Volts EXTBATTS : 0 FIRMWARE : 60.11.I END APC : 2012-05-20 22:30:02 +0300